Engine Start Sequence
|
Cyclic cranking: 7 sec. on, 7 sec. rest. 90 sec. maximum duration
|
|
Automatic Low Oil Shutdown
|
Standard
|
|
Overspeed Shutdown
|
Standard, 72 Hz
|
|
Overcrank Protection
|
Standard
|
|
Automatic Voltage Regulator with Over-Voltage Protection
|
Standard
|
|
Engine Warmup
|
10 seconds
|
|
Engine Cool-Down
|
1 minute
|
|
Safety Fuse
|
Standard
|
|
Starter Lockout
|
Starter cannot re-engage until 5 seconds after the engine has stopped
|
|
2.5 Amp Timed Trickle Battery Charger
|
Standard
|
|
WhisperTest�
|
Sound Output is 61 dB(A) at 23 ft. with generator in WhisperTest� exercise mode
|
|
Auto Switch
|
Automatic start on utility failure/7 day exercise
|
|
Off Switch
|
Stops unit. Power is removed. Control and charger still operate
|
|
Manual / Test (start)
|
Start with starter control, unit stays on. If utility fails, transfer
to load takes place |
|
Full Monitoring System
|
Oil pressure, coolant temperature, engine speed, coolant level,
cranking time, starter lockout, utility sensing |
|
Shutdown and LED Indicators
|
Overspeed and overcrank, low oil pressure, high coolant temperature,
low coolant level, low fuel pressure, low battery voltage |
|
|
 |
 |
 |
 |
|
 |

|